Separate Amplifier Type Pressure Sensor

AP-40 series

Catalogues View Catalogue

This model has been discontinued.
Compliance with the certification standard is ensured as of the time of shipment from our company.

Recommended Replaceable Products: Network Compatible Pressure Sensor - AP-N series

Amplifier Unit NPN AP-40RA

AP-40RA - Amplifier Unit NPN

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Data Sheet (PDF)

Manuals

CAD Data

360°view (3D PDF)

  • CE Marking

Specifications

Model

AP-40RA

Type

Zero shift focus type, NPN

Applicable sensor head

AP-41M, AP-41, AP-43, AP-44, AP-48

Rated pressure

-15% to +110% of F.S.

Display

3 1/2-digit, 2-colour, 7-segment LED (Character height: 11 mm), Display cycle: 5 times/sec.

Display resolution

AP-41/41M: 0.1 kPa, AP-43: 0.001 Mpa, AP-44/48: 0.2 kPa*1

Display temperature characteristic

±1.0 % max. of F.S.

Mounting

With supplied mounting bracket (2 types) or optional panel mounting bracket*2

Response time (Chattering prevention function)

2.5/5/100/500 msec

I/O

Zero-shift input

Input time: 20 ms or more

Control output

NPN open-collector: 100 mA max. (40 V max.),
Residual voltage: 1 V max. 2-output (N.O./N.C. selectable)

Analogue voltage output

1 to 5 V*3

Rating

Power voltage

12 to 24 VDC ±10 %, Ripple 10 % or less

Current consumption

105 mA (12 V), 55 mA (24 V) (including sensor head)

Environmental resistance

Ambient temperature

0 to +50 °C (No freezing)

Relative humidity

35 to 85 % RH

Vibration resistance

10 to 55 Hz, Double amplitude 1.5 mm, 2 hours in each of the X, Y, and Z axis

Shock resistance

100 m/s2, 3 times in each of X, Y and Z axis

Material

Front housing: Polyamide, Front panel sheet: PET, Rear housing: Polysulfone, Cable: Oil-proof cabtyre cable

Weight

80 g (including 2 m cable) (28 g without cable)

*1 Refer to the following table for the resolution in the zero-shift focus mode of the AP-40RA.
Display range: ±19.9% from the middle of the shift input value (within the sensor head rating)
Display resolution: 0.01 kPa [AP-41/41M], 0.1 kPa (0.0001 Mpa) [AP-43], 0.02 kPa [AP-44/48]
*2 Optional panel mounting brackets: OP-31357 (black), OP-32808 (gray) and OP-42192 (for a 5 mm-thick panel)
*3 The AP-48 is only compatible with the AP-40RA. It cannot be used with an analogue output amplifier.

Data Sheet (PDF) Other Models