Touch Panel Display
VT3 series
Specs Touch Panel Display VT3 series
Model |
VT3-V8 |
VT3-V7 |
VT3-V7R |
|||
Image |
|
|
|
|||
General specifications |
Current consumption |
950mA or less |
800mA or less |
550mA or less |
||
Structure |
Panel built-in type, IP65f equivalent dust-proof, waterjet-proof |
IP65f equivalent dust proof, waterjet proof |
||||
Overvoltage category |
I |
|||||
Pollution degree |
2 |
3 |
||||
Power voltage |
24 VDC ±10% |
|||||
Noise resistance |
1500 Vp-p pulse width 1 µs 50 ns (common mode, based on noise simulator) |
|||||
Withstand voltage |
1500 VAC 1 minute (between power terminal and housing) |
|||||
Insulation resistance |
50 MΩ or more tested by 500 VDC megohmmeter (between power terminal and housing) |
|||||
Vibration resistance |
Intermittent vibration |
Frequency: 5 to 9 Hz |
Half amplitude:3.5 mm*1 |
|||
Frequency: 9 to 150 Hz |
Acceleration: 9.8 m/s2 *1 |
|||||
Continuous vibration |
Frequency: 5 to 9 Hz |
Half amplitude:1.75 mm*1 |
||||
Frequency: 9 to 150 Hz |
Acceleration: 4.9 m/s2 *1 |
|||||
Ground |
― |
Class D grounding (Class 3 grouding). |
||||
Operating environment |
Minimal amount of dust and corrosive gas present |
|||||
Ambient operating temperature |
0 to +50°C |
|||||
Ambient operating humidity |
35 to 85%RH (No condensation)*2 |
|||||
Ambient storage temperature |
-10 to +60°C (No freezing) |
|||||
Ambient storage humidity |
35 to 85%RH (No condensation)*2 |
|||||
Weight |
Approx 1250 g |
Approx 1150 g |
Approx 1,600 g (excluding the cable) |
|||
Performance specifications |
Displaypanel |
Display elements |
TFT colour LCD |
|||
Display colour |
32768 colours |
|||||
Number of points displayed |
W 640 × H 480 points |
|||||
Active display area |
W 170.9 × H 128.2 mm |
W 151.7 × H 113.8 mm |
||||
Service life (normal temperature andhumidity) |
Approx 50000 h |
|||||
Backlightlamp |
System |
White LED (Not replaceable)*3 |
White LED (Not replaceable) |
Cold-cathode tube (Not replaceable) |
||
Life-span |
Approx 50000 h |
Approx 54000 h |
||||
Touchswitch |
Number of switches |
40×30/screen |
||||
System |
Matrix resistive film |
|||||
Operating force |
0.98N or less |
|||||
Life-span |
1,000,000 times or more |
|||||
External calibration input signal |
― |
Pressure-sensitive type |
||||
Screen data internal memory |
Memory capacity |
12 MB (memory extension enabled) |
||||
Number of pages that can be registered |
Up to 1024 pages |
|||||
Number of screens that can be registered |
Up to 1024 screens |
|||||
Page No.: 0 to 8999, Global window No.: G000 to G999, Report screen P.00 to P.15 |
||||||
Data backup |
Screen data |
Flash ROM can be erased 100000 times. |
||||
Recording data |
SRAM backup:lithium battery |
|||||
Character font |
Outline font, Bitmap font, Stroke font Windows font, IMAGE font, Small font |
|||||
Calendar timer |
Accuracy: ±40s/month (25°C), Backup:lithium battery (5 years above of service life at 25°C) |
|||||
Communication function |
PLC host link |
KEYENCE, Mitsubishi Electric, OMRON, Sharp, Fuji Electric FA Components & Systems, Yaskawa Electric, Hitachi, Panasonic Electric Works, JTEKT (Toyota), |
||||
Thermostat |
Yokogawa Electric, Azbil (Yamatake), OMRON, RKC Instrument, Shinko Technos, CHINO |
|||||
Inverter |
Mitsubishi Electric, Fuji Electric FA Components & Systems, Yaskawa Electric, OMRON |
|||||
Servo amplifier |
Mitsubishi Electric |
|||||
Stepping motor |
Orienltal Motor |
|||||
Robot controller |
IAI |
|||||
Eco-power meter |
Panasonic Electric Works |
|||||
General-purpose communication |
Based on specific commands |
|||||
Grip switch |
Life-span |
― |
50,000 times or more |
|||
Arrow keys |
Life-span |
100,000 times or more |
||||
I/O specifications |
Serial I/F (PORT 1: SERIAL) for connecting PCs |
Applied standard |
Conforms to EIA RS-232C |
― |
||
Synchronisation between the transmitter and receiver |
Start-stop, full duplex |
|||||
Communication distance |
15m |
|||||
Data length |
7 or 8 bits |
― |
||||
Parity |
Even, odd, none |
|||||
Communication speed |
1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps |
|||||
Serial I/F (PORT 2) for connecting PLC/external devices |
Applied standard |
Conforms to EIA RS-232C and RS-422A |
||||
Synchronisation between the transmitter and receiver |
Start-stop, full duplex |
|||||
Communication distance |
15m (RS-232C)/500m (RS-422A) |
|||||
Data length |
7 or 8 bits |
― |
||||
Parity |
Even, odd, none |
|||||
Communication speed |
1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps |
|||||
Serial I/F (PORT 3) for connecting barcode/PLC/external devices |
Applied standard |
Conforms to EIA RS-232C*4 |
||||
Synchronisation between the transmitter and receiver |
Start-stop, full duplex |
|||||
Communication distance |
15 m*5 |
|||||
Data length |
7 or 8 bits |
|||||
Parity |
Even, odd, none |
|||||
Communication speed |
1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps |
|||||
Serial I/F (PORT 4) for connecting MegaLink/multi-link/KL-link/external devices |
When connected through MegaLink |
Applied standard |
RS-485 |
|||
Synchronisation between the transmitter and receiver |
Start-stop, half duplex |
― |
||||
Communication speed |
19,200 bps, 115,200 bps, 0.5 Mbps, 1 Mbps, 2 Mbps |
|||||
Cable connection |
Multi-drop (branching is not possible) |
|||||
Maximum number of connectable units |
15 |
|||||
Baud rate 19200 |
Maximum extension distance: 1,000 m |
|||||
Baud rate 115200 |
||||||
Baud rate 0.5 M |
Maximum extension distance: 500 m |
|||||
Baud rate 1 M |
Maximum extension distance: 200 m |
|||||
Baud rate 2 M |
Maximum extension distance: 100 m |
|||||
When connected through VT2 multi-link |
Applied standard |
RS-485 |
||||
Synchronisation between the transmitter and receiver |
Start-stop, half duplex |
― |
||||
Communication distance |
Maximum extension distance: 500 m or less |
|||||
Communication speed |
19200, 115200, 0.5M, 1M bit/s |
|||||
Baud rate 115200 or less |
Maximum extension distance: 500 m |
|||||
Baud rate 0.5 M |
Maximum extension distance: 100 m |
|||||
Baud rate 1 M |
Maximum extension distance: 50 m |
|||||
When connected through multi-link |
Applied standard |
RS-485 |
||||
Synchronisation between the transmitter and receiver |
Start-stop, half duplex |
― |
||||
Communication distance |
Maximum extension distance: 500 m or less |
|||||
Communication speed |
19200, 38400, 57600, 115200 bit/s |
|||||
When linked with the KL |
Sign system |
f, f/2 encoding |
― |
|||
Control method |
Autonomous distributed token bus control |
|||||
Cable connection |
T-shaped branch, multi-drop |
|||||
Communication speed |
5 Mbps, 2.5 Mbps, 625 kbps, 156 kbps |
|||||
Communication media |
Dedicated cable KPEV-SB (1 pc; 2-core shielded twisted pair cable [stranded wire]) * Conductor section area: 0.5 to 1.25 mm2 |
|||||
Maximum number of connectable units |
129 units (including the master station, not including the KL-T1) |
|||||
Error control |
Vertical parity, checksum, double sampling, burst noise detection |
|||||
Baud rate 5 Mbit/s: Maximum base length |
50 m |
|||||
Baud rate 5 Mbit/s: Maximum branch wire length |
20 m |
|||||
Baud rate 2.5 Mbit/s: Maximum base length |
120 m |
|||||
Baud rate 2.5 Mbit/s: Maximum branch wire length |
40 m |
|||||
Baud rate 625 kbit/s: Maximum base length |
500 m |
|||||
Baud rate 625 kbit/s: Maximum branch wire length |
150 m |
|||||
Baud rate 156 kbit/s: Maximum base length |
1200 m |
|||||
Baud rate 156 kbit/s: Maximum branch wire length |
350 m |
|||||
Communication cable conductor section area 0.5 mm2 |
Maximum extension distance: 1,000 m |
― |
||||
Communication cable conductor section area 0.75 mm2 |
Maximum extension distance: 1,200 m |
|||||
Communication cable conductor section area 0.9 mm2 |
||||||
Communication cable conductor section area 1.25 mm2 |
||||||
*1 Conforms to JIS B 3502, IEC61131-2 |
Model |
VT3-V6H |
VT3-V6HG |
VT3-Q5H |
|||
Image |
|
|
|
|||
General specifications |
Current consumption |
380mA or less |
250mA or less |
|||
Structure |
IP65f equivalent dust proof, waterjet proof |
|||||
Overvoltage category |
I |
|||||
Pollution degree |
3 |
|||||
Power voltage |
24 VDC ±10% |
|||||
Noise resistance |
1500 Vp-p pulse width 1 µs 50 ns (common mode, based on noise simulator) |
|||||
Withstand voltage |
1500 VAC 1 minute (between power terminal and housing) |
|||||
Insulation resistance |
50 MΩ or more tested by 500 VDC megohmmeter (between power terminal and housing) |
|||||
Vibration resistance |
Intermittent vibration |
Frequency: 5 to 9 Hz |
Half amplitude:3.5 mm*1 |
|||
Frequency: 9 to 150 Hz |
Acceleration: 9.8 m/s2*1 |
|||||
Continuous vibration |
Frequency: 5 to 9 Hz |
Half amplitude:1.75 mm*1 |
||||
Frequency: 9 to 150 Hz |
Acceleration: 4.9 m/s2 *1 |
|||||
Ground |
Class D grounding (Class 3 grouding). |
|||||
Operating environment |
Minimal amount of dust and corrosive gas present |
|||||
Ambient operating temperature |
0 to +50°C *2*3 |
0 to +50°C*3 |
||||
Ambient operating humidity |
35 to 85%RH (No condensation)*4*3 |
|||||
Ambient storage temperature |
-10 to +60°C (No freezing) |
|||||
Ambient storage humidity |
35 to 85%RH (No condensation)*4*3 |
|||||
Drop |
According to JIS B 3502 IEC61131-2 (1.3m) |
|||||
Weight |
Approx 1100g*5 |
Approx 1120 g*5 |
Approx 970g*5 |
|||
Performance specifications |
Displaypanel |
Display elements |
TFT colour LCD |
|||
Display colour |
32768 colours |
|||||
Number of points displayed |
W 640 × H 480 points |
W 320 × H 240 points |
||||
Active display area |
W 132.5 × H 99.4 mm |
W 115.2 × H 86.4 mm |
||||
Service life (normal temperature andhumidity) |
Approx 50000 h |
|||||
Backlightlamp |
System |
White LED (Not replaceable) |
||||
Life-span |
Approx 50000 h |
|||||
Touchswitch |
Number of switches |
80×60/screen |
40×30/screen |
|||
System |
Analogue resistive membrane type |
|||||
Operating force |
0.98N or less |
|||||
Life-span |
1,000,000 times or more |
|||||
Screen data internal memory |
Memory capacity |
12 MB (memory extension enabled) |
4 MB (memory extension enabled) |
|||
Number of pages that can be registered |
Up to 1024 pages |
|||||
Number of screens that can be registered |
Up to 1024 screens |
|||||
Page No.: 0 to 8999, Global window No.: G000 to G999, Report screen P.00 to P.15 |
||||||
Data backup |
Screen data |
Flash ROM can be erased 100000 times. |
||||
Recording data |
SRAM backup:lithium battery |
|||||
Character font |
Outline font, Bitmap font, Stroke font Windows font, IMAGE font, Small font |
|||||
Calendar timer |
Accuracy: ±40s/month (25°C), Backup:lithium battery (5 years above of service life at 25°C) |
|||||
Communication function |
PLC host link |
KEYENCE, Mitsubishi Electric, OMRON, Sharp, Fuji Electric FA Components & Systems, Yaskawa Electric, Hitachi, Panasonic Electric Works, JTEKT (Toyota), |
||||
Thermostat |
Yokogawa Electric, Azbil (Yamatake), OMRON, RKC Instrument, Shinko Technos, CHINO |
|||||
Inverter |
Mitsubishi Electric, Fuji Electric FA Components & Systems, Yaskawa Electric, OMRON |
|||||
Servo amplifier |
Mitsubishi Electric |
|||||
Stepping motor |
Orienltal Motor |
|||||
Robot controller |
IAI |
|||||
Eco-power meter |
Panasonic Electric Works |
|||||
General-purpose communication |
Based on specific commands |
|||||
I/O specifications |
Function switch (FSW1/FSW2/FSW5/FSW6) |
Number of outputs |
4 (FSW1, FSW2, FSW5, FSW6) |
|||
Common terminal |
4 terminals/common (FSWC) |
|||||
Output |
MOSFET (N-ch; with overcurrent protection function) |
|||||
Rated load |
30 VDC 0.1 A |
|||||
Leakage current (at OFF) |
100 µA or less |
|||||
Residual voltage (at ON) |
1.0V or less |
|||||
Durability |
300,000 times or more |
|||||
Enabling switch (EN1A/EN1B/EN2A/EN2B) |
Rated voltage |
30 VCD |
30 VDC |
30 VCD |
||
Rated current |
― |
1 A (resistive load), 0.7 A (inductive load) |
― |
|||
Contact method |
2a contact |
|||||
Durability |
Mechanical |
Position 1 -> 2 -> 1: 1,000,000 times or more, position 1 -> 2 -> 3 -> 1: 100,000 times or more |
||||
Electrical |
100,000 times or more |
|||||
Function |
The following 3-position-operation is available: position 1: off (when not pressed), position 2: on (when pressed to the middle position), position 3: off (when pressed as far as possible). * When the position returns from position 3 (when pressed as far |
|||||
RS-232C/422 communication (CN2A/CN2B) |
Applied standard |
Conforms to EIA RS-232C and RS-422 |
||||
Synchronisation between the transmitter and receiver |
Start-stop, full duplex |
|||||
Communication distance |
15m (RS-232C)/500m (RS-422) |
|||||
Data length |
7 or 8 bits |
|||||
Parity |
Even, odd, none |
|||||
Communication speed |
1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps |
|||||
Ethernet communication (CN3) |
Compliance |
IEEE802.3 |
||||
Transmission speed |
10 Mbps (10BASE-T),100 Mbps (100BASE-TX) |
|||||
Transmission medium |
STP or category 3 or higher UTP (10BASE-T), STP or category 5 or higher UTP (100BASE-TX)*6 |
|||||
Maximum cable length |
100 m |
|||||
Maximum number of connectable hubs |
4 (10BASE-T),2 (100BASE-TX) |
|||||
Maximum number of connections |
PC application:*7 3, |
|||||
MegaLink/multi-link (A/B/G) |
When connected through MegaLink |
Applied standard |
RS-485 |
|||
Synchronisation between the transmitter and receiver |
Start-stop, half duplex |
|||||
Communication speed |
19,200 bps, 115,200 bps, 0.5 Mbps, 1 Mbps, 2 Mbps |
|||||
Cable connection |
Multi-drop (branching is not possible) |
|||||
Maximum number of connectable units |
15 |
|||||
Baud rate 19200 |
Maximum extension distance: 1,000 m |
|||||
Baud rate 115200 |
||||||
Baud rate 0.5 M |
Maximum extension distance: 500 m |
|||||
Baud rate 1 M |
Maximum extension distance: 200 m |
|||||
Baud rate 2 M |
Maximum extension distance: 100 m |
|||||
When connected through VT multi-link |
Applied standard |
RS-485 |
||||
Synchronisation between the transmitter and receiver |
Start-stop, half duplex |
|||||
Communication distance |
Maximum extension distance: 500 m or less |
|||||
Communication speed |
19200, 115200, 0.5M, 1M bit/s |
|||||
Baud rate 115200 or less |
Maximum extension distance: 500 m |
|||||
Baud rate 0.5 M |
Maximum extension distance: 100 m |
|||||
Baud rate 1 M |
Maximum extension distance: 50 m |
|||||
When connected through multi-link |
Applied standard |
RS-485 |
||||
Synchronisation between the transmitter and receiver |
Start-stop, half duplex |
|||||
Communication distance |
Maximum extension distance: 500 m or less |
|||||
Communication speed |
19200, 38400, 57600, 115200 bit/s |
|||||
*1 Conforms to JIS B 3502, IEC61131-2 |
Model |
VT3-W4T |
VT3-W4TA |
VT3-W4MT |
VT3-W4MTA |
|||
Image |
|
|
|
|
|||
General specifications |
Current consumption |
200mA or less |
|||||
Structure |
Panel built-in type, IP65f equivalent dust-proof, waterjet-proof on only front panel |
||||||
Overvoltage category |
I |
||||||
Pollution degree |
2 |
||||||
Power voltage |
24 VDC ±10% |
||||||
Noise resistance |
1500 Vp-p pulse width 1 µs (common mode, based on noise simulator) |
||||||
Withstand voltage |
1500 VAC 1 minute (between power terminal and housing) |
||||||
Insulation resistance |
50 MΩ or more tested by 500 VDC megohmmeter (between power terminal and housing) |
||||||
Vibration resistance |
Intermittent vibration |
Frequency: 5 to 9 Hz |
Half amplitude:3.5 mm*1 |
||||
Frequency: 9 to 150 Hz |
Acceleration:9.8 m/s2 *1 |
||||||
Continuous vibration |
Frequency: 5 to 9 Hz |
Half amplitude:1.75 mm*1 |
|||||
Frequency: 9 to 150 Hz |
Acceleration:4.9 m/s2 *1 |
||||||
Operating environment |
Minimal amount of dust and corrosive gas present |
||||||
Ambient operating temperature |
0 to +50°C |
||||||
Ambient operating humidity |
35 to 85%RH (No condensation)*2 |
||||||
Ambient storage temperature |
-20 to +60°C (No freezing) |
||||||
Ambient storage humidity |
35 to 85%RH (No condensation)*2 |
||||||
Weight |
Approx 250 g |
||||||
Performance specifications |
Displaypanel |
Display elements |
TFT LCD |
||||
Display colour |
32768 colours |
32 greyscale |
|||||
Number of points displayed |
W 320 × H 128 points |
||||||
Active display area |
W 110.4 × H 44.2 mm |
||||||
Service life (normal temperature andhumidity) |
Approx 50000 h |
||||||
Backlightlamp |
System |
White LED (Not replaceable) |
|||||
Life-span |
Approx 50000 h |
||||||
Display colour |
― |
3 colours (white/pink/red) |
|||||
Touchswitch |
Number of switches |
40×16/screen |
|||||
System |
Analogue resistive membrane type |
||||||
Operating force |
0.98N or less |
||||||
Life-span |
1,000,000 times or more |
||||||
Screen data internal memory |
Memory capacity |
3 MB |
|||||
Number of pages that can be registered |
Up to 1024 pages |
||||||
Number of screens that can be registered |
Up to 1024 screens |
||||||
Page No.: 0 to 8999, Global window No.: G000 to G999 |
|||||||
Data backup |
Screen data |
Flash ROM can be erased for 100000 times |
|||||
Recording data |
SRAM backup:lithium battery |
||||||
Character font |
Outline font, Bitmap font, Windows font, IMAGE font, Small font |
||||||
Calendar timer |
Accuracy:±40s/month (25°C), Backup:1lithium battery (5 years above of service life at 25°C) |
||||||
Communication function |
PLC host link |
KEYENCE, Mitsubishi Electric, OMRON, Sharp, Fuji Electric FA Components & Systems, Yaskawa Electric, Hitachi, Panasonic Electric Works, JTEKT (Toyota), |
|||||
Thermostat |
Yokogawa Electric, Azbil (Yamatake), OMRON, RKC Instrument, Shinko Technos, CHINO |
||||||
Inverter |
Mitsubishi Electric, Fuji Electric FA Components & Systems, Yaskawa Electric, OMRON |
||||||
Servo amplifier |
Mitsubishi Electric |
||||||
Stepping motor |
Oriental Motor |
||||||
Robot controller |
IAI |
||||||
Eco-power meter |
Panasonic Electric Works |
||||||
General-purpose communication |
Based on specific commands |
||||||
I/O specifications |
Serial I/F (PORT 2) for connecting PLC/MegaLink/multi-link/external devices |
Applied standard |
― |
Conforms to EIA RS-422A and RS-485 |
― |
Conforms to EIA RS-422A and RS-485 |
|
Synchronisation between the transmitter and receiver |
RS-422A: start-stop, full duplex; RS-485: start-stop, half duplex |
RS-422A: start-stop, full duplex; RS-485: start-stop, half duplex |
|||||
Transmission distance |
RS-422A: 500 m, RS-485: 1,000 m |
RS-422A: 500 m, RS-485: 1,000 m |
|||||
Data length |
7 or 8 bits |
7 or 8 bits |
|||||
Parity |
Even, odd, none |
Even, odd, none |
|||||
Transmission speed |
1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps |
1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps |
|||||
When connected through MegaLink |
Applied standard |
RS-485 |
|||||
Synchronisation between the transmitter and receiver |
― |
Start-stop, half duplex |
― |
Start-stop, half duplex |
|||
Communication speed |
19,200, 115,200 bps |
19,200, 115,200 bps |
|||||
Connection format |
Multi-drop (branching is not possible) |
Multi-drop (branching is not possible) |
|||||
Maximum number of connectable units |
15 |
15 |
|||||
Baud rate 19200 |
Maximum extension distance: 1,000 m |
Maximum extension distance: 1,000 m |
|||||
Baud rate 115200 |
|||||||
When connected through VT2 multi-link |
Communication speed |
19,200, 115,200 bps |
19,200, 115,200 bps |
||||
When connected through multi-link |
Applied standard |
RS-485 |
RS-485 |
||||
Synchronisation between the transmitter and receiver |
Start-stop, half duplex |
Start-stop, half duplex |
|||||
Communication distance |
Maximum extension distance: 500 m or less |
Maximum extension distance: 500 m or less |
|||||
Communication speed |
19,200, 38,400, 57,600, 115,200 bps |
19,200, 38,400, 57,600, 115,200 bps |
|||||
Serial I/F (PORT 2) for connecting PLC/external devices |
Applied standard |
Conforms to EIA RS-232C |
― |
Conforms to EIA RS-232C |
― |
||
Synchronisation between the transmitter and receiver |
Start-stop, half duplex |
Start-stop, half duplex |
|||||
Communication distance |
15m |
||||||
Data length |
7 or 8 bits |
― |
7 or 8 bits |
― |
|||
Parity |
Even, odd, none |
Even, odd, none |
|||||
Communication speed |
1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps |
1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps |
|||||
*1 Conforms to JIS B 3502, IEC61131-2 |