Model | VT-T1 | |||
General specifications | Current consumption | VT-T1: 50 mA or less, VT3-V6H (G) + VT-T1: 430 mA or less, VT3-Q5H (G) + VT-T1: 300 mA or less | ||
Structure | Panel-mount type (Only the front part. When checking the connectors, the construction has dustproofing and splashproofing equivalent to IP65f.) and DIN-mount type | |||
Overvoltage category | I | |||
Pollution degree | 3 | |||
Power voltage | 24 VDC ±10% | |||
Noise resistance | 1,500 Vp-p or more, pulse width: 1 µs, 50 ns (by way of a noise simulator) | |||
Withstand voltage | 1500 VAC 1 minute (between power terminal and housing) | |||
Insulation resistance | 50 MΩ or more tested by 500 VDC megohmmeter (between power terminal and housing) | |||
Vibration resistance | Intermittent vibration | Frequency: 5 to 9 Hz | Half amplitude: 3.5 mm*1 | |
Frequency: 9 to 150 Hz | Acceleration: 9.8 m/s2*1 | |||
Continuous vibration | Frequency: 5 to 9 Hz | Half amplitude: 1.75 mm*1 | ||
Frequency: 9 to 150 Hz | Acceleration: 4.9 m/s2 *1 | |||
Ground | Class D grounding | |||
Operating environment | Minimal amount of dust and corrosive gas present | |||
Ambient operating temperature | 0 to +50°C | |||
Ambient operating humidity | 35 to 85%RH (No condensation)*2 | |||
Ambient storage temperature | -10 to +60°C (No freezing) | |||
Ambient storage humidity | 35 to 85%RH (No condensation)*2 | |||
Weight | Approx 410 g | |||
Performance specifications | Can be used to enable and disable the emergency stop push-button switch | A key switch can be used to enable and disable the emergency stop pushbutton switch. | ||
Power supply ON/OFF switching | A key switch can be used to turn the power supply to the VT3 handy series on and off. | |||
Cable wiring terminal block conversion | Cable wiring has been changed to a terminal block. | |||
I/O specifications | PLC communication cable connection connector | Applied standard | Conforms to EIA RS-232C and RS-422 | |
Synchronization between the transmitter and receiver | Start-stop, full duplex | |||
Communication distance | 15m (RS-232C)/500m (RS-422)*3 | |||
Data length | 7 or 8 bits | |||
Parity | Even, odd, none | |||
Communication speed | 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps | |||
Ethernet connector | Compliance | IEEE802.3 | ||
Transmission speed | 10 Mbps (10BASE-T),100 Mbps (100BASE-TX) | |||
Transmission medium | STP or category 3 or higher UTP (10BASE-T), STP or category 5 or higher UTP (100BASE-TX)*4 | |||
Maximum cable length | 100 m*5 | |||
Maximum number of connectable hubs | 4 (10BASE-T),2 (100BASE-TX) | |||
Maximum number of connections | PC application:*6 3, | |||
MegaLink (A/B/G) | Applied standard | RS-485 | ||
Synchronization between the transmitter and receiver | Start-stop, half duplex | |||
Communication speed | 19,200 bps, 115,200 bps, 0.5 Mbps, 1 Mbps, 2 Mbps | |||
Cable connection | Multi-drop (branching is not possible) | |||
Maximum number of connectable units | 15 | |||
Baud rate 19200 | Maximum extension distance: 1,000 m*5 | |||
Baud rate 115200 | ||||
Baud rate 0.5 M | Maximum extension distance: 500 m*5 | |||
Baud rate 1 M | Maximum extension distance: 200 m*5 | |||
Baud rate 2 M | Maximum extension distance: 100 m*5 | |||
VT2 multi-link (A/B/G) | Applied standard | RS-485 | ||
Synchronization between the transmitter and receiver | Start-stop, half duplex | |||
Communication distance | Maximum extension distance: 500 m*5 | |||
Communication speed | 19200, 115200, 0.5M, 1M bit/s | |||
Baud rate 115200 or less | Maximum extension distance: 500 m*5 | |||
Baud rate 0.5 M | Maximum extension distance: 100 m*5 | |||
Baud rate 1 M | Maximum extension distance: 50 m*5 | |||
Multi-link (A/B/G) | Applied standard | RS-485 | ||
Synchronization between the transmitter and receiver | Start-stop, half duplex | |||
Communication distance | Maximum extension distance: 500 m*5 | |||
Communication speed | 19200, 38400, 57600, 115200 bit/s | |||
Emergency stop push-button switch monitor (TPAM/TPBM) | Rated voltage | 30 VDC | ||
Rated current | 1 A (resistive load) | |||
Contact method | 1a contact | |||
Durability | Mechanical | 50,000,000 times or more | ||
Electrical | 100,000 times or more | |||
Key switch monitor (TKAM/TKBM) | Rated voltage | 30 VDC | ||
Rated current | 1 A (resistive load) | |||
Contact method | 1a contact | |||
Durability | Mechanical | 20,000,000 times or more | ||
Electrical | 100,000 times or more | |||
*1 Conforms to JIS B 3502, IEC61131-2 |